Pt100 vs Pt1000: Differences, Accuracy and When to Use Each

What is the difference?

Both Pt100 and Pt1000 are platinum RTDs. The number refers to the nominal resistance at 0 °C:

  • Pt100: 100 Ω at 0 °C
  • Pt1000: 1000 Ω at 0 °C

They use the same platinum resistance principle and the same accuracy classes, but the higher resistance of Pt1000 changes how the sensor behaves in a real installation.

Why resistance matters

The resistance of the cable and connections adds to the measured resistance. For a Pt100, a small cable resistance is a larger percentage of the total signal. For a Pt1000, the same cable resistance is a smaller percentage, so a 2-wire Pt1000 can be more forgiving on short cable runs.

However, a higher resistance also means more self-heating for the same measurement current. Good transmitters and meters limit the excitation current, but self-heating can matter in still air or in small probes.

Comparison at a glance

  • Resistance: Pt100 = 100 Ω, Pt1000 = 1000 Ω at 0 °C
  • Cable sensitivity: Pt1000 is less affected by cable resistance
  • Self-heating: Pt1000 can generate more heat for the same current; check the instrument
  • Compatibility: Pt100 is the more common industrial standard; Pt1000 is common in HVAC, appliances and compact electronics
  • Accuracy: both are available in Class A, Class B and tighter tolerances

When to choose Pt100

  • General industrial probes and transmitters
  • Applications where the instrument is specified for Pt100
  • Long cable runs with a 3- or 4-wire connection
  • Replacement parts for existing Pt100 systems

See our Pt100 probe sensors and Pt100 transmitters.

When to choose Pt1000

  • HVAC and building controls
  • Appliance and compact electronic products
  • Short cable runs where a 2-wire connection is acceptable
  • Battery-powered or low-power devices with a suitable measurement circuit

Wiring and accuracy

For either element, the wiring method matters more than the nominal resistance:

  • 2-wire: simplest, but cable resistance adds error
  • 3-wire: compensates for cable resistance in industrial probes
  • 4-wire: best accuracy for laboratory and long cables

If you need the best accuracy, choose a 4-wire Pt100 or Pt1000 and calibrate the complete probe.