Pt100 vs Pt1000: Differences, Accuracy and When to Use Each
What is the difference?
Both Pt100 and Pt1000 are platinum RTDs. The number refers to the nominal resistance at 0 °C:
- Pt100: 100 Ω at 0 °C
- Pt1000: 1000 Ω at 0 °C
They use the same platinum resistance principle and the same accuracy classes, but the higher resistance of Pt1000 changes how the sensor behaves in a real installation.
Why resistance matters
The resistance of the cable and connections adds to the measured resistance. For a Pt100, a small cable resistance is a larger percentage of the total signal. For a Pt1000, the same cable resistance is a smaller percentage, so a 2-wire Pt1000 can be more forgiving on short cable runs.
However, a higher resistance also means more self-heating for the same measurement current. Good transmitters and meters limit the excitation current, but self-heating can matter in still air or in small probes.
Comparison at a glance
- Resistance: Pt100 = 100 Ω, Pt1000 = 1000 Ω at 0 °C
- Cable sensitivity: Pt1000 is less affected by cable resistance
- Self-heating: Pt1000 can generate more heat for the same current; check the instrument
- Compatibility: Pt100 is the more common industrial standard; Pt1000 is common in HVAC, appliances and compact electronics
- Accuracy: both are available in Class A, Class B and tighter tolerances
When to choose Pt100
- General industrial probes and transmitters
- Applications where the instrument is specified for Pt100
- Long cable runs with a 3- or 4-wire connection
- Replacement parts for existing Pt100 systems
See our Pt100 probe sensors and Pt100 transmitters.
When to choose Pt1000
- HVAC and building controls
- Appliance and compact electronic products
- Short cable runs where a 2-wire connection is acceptable
- Battery-powered or low-power devices with a suitable measurement circuit
Wiring and accuracy
For either element, the wiring method matters more than the nominal resistance:
- 2-wire: simplest, but cable resistance adds error
- 3-wire: compensates for cable resistance in industrial probes
- 4-wire: best accuracy for laboratory and long cables
If you need the best accuracy, choose a 4-wire Pt100 or Pt1000 and calibrate the complete probe.
Ordering tips
Tell us:
- Element: Pt100 or Pt1000
- Accuracy class: A, B, 1/3B or tighter
- Wiring: 2, 3 or 4 wire
- Probe diameter, length and thread
- Cable length and insulation
- Temperature range and environment
We supply Pt100/Pt1000 elements and complete probes. Contact us with your specification and we will recommend the closest standard or custom build.